Ask a Powder Pro: When do I need to redo or update a Dust Hazard Analysis?

Conducting a Dust Hazard Analysis (DHA) is not a once in a lifetime event, as process changes may require updates to your hazard assessment.

National Fire Protection Association (NFPA) standards require that any facility handling combustible dust must complete a DHA. Specifically, NFPA 660, Standard on Combustible Dusts and Particulate Solids, offers guidance on industry best practices and how to complete a DHA. Companies handling potentially combustible dust are responsible for determining their particular material’s combustibility and the fire and explosion hazards in their processes, which NFPA standards cover extensively. Many companies turn to safety experts outside their organization for completing the DHA and for updates.

The minimum requirement for reviewing and updating your DHA is at least every five years, according to NFPA 660. This minimum threshold is often referred to as a DHA revalidation. If no changes have been made to your process, the revalidation may be simpler than the original hazard analysis.

A DHA revalidation involves first reviewing the previous hazard analysis. It is important to understand any assumptions and findings made in the previous report to determine if they are accurate or have been properly addressed after the last DHA was completed. Next, an on-site analysis is conducted to determine if the process is the same as in the previous DHA and to evaluate any changes. After the on-site analysis is completed, a reassessment of the hazards is required, which includes evaluating the potential ignition sources, administrative controls, protection systems, and new, emerging hazards. Finally, a check against new regulatory documents should be included because new standards will incorporate the latest best practices for combustible dust safety and compliance. Once completed, a new DHA report is issued that should provide a clear roadmap to understand the hazards present and systems currently in place to prevent or mitigate those hazards.

Keep in mind that waiting for five years before revalidation may not be appropriate for proper safety. Other events may trigger an update and review of your DHA, which could include:

Process modifications. Changing a process or adding a new process may introduce new hazards to a facility. New processes should have a desktop DHA conducted, which may require a subsequent on-site DHA to validate the original assessment.

Introduction of new or different versions of powders. Changing the particle size, moisture content, or type of powder can greatly alter the hazard presented by combustible dust.

Replacement of existing process equipment. If equipment is not changed with a comparable or “replacement-in-kind” solution, a Management of Change (MOC) process should trigger a review and possible modification of the DHA.

A near miss or incident. Having an incident or near-miss incident may require a review and modification of your existing DHA. Even though a DHA should be conducted by a qualified person, something may occur that was unforeseen and should be reviewed.

Revalidation is a valuable tool when addressing safety over the long term and can prevent overlooking hazards that lead to catastrophic incidents impacting a plant’s processes and, more importantly, workers.

About the Author

Jason Krbec

Jason Krbec

Sales engineering manager

Jason Krbec, PE, is director of business development at CV Technology and is a licensed professional engineer in the state of Florida. He holds a B.S. in mechanical engineering from the University of Florida and is an active NFPA technical committee member.